Designing a conveyor system involves more than just bolting a motor to a frame. If you undersize the motor, it won't start under load due to breakaway torque. If you oversize it, you waste thousands on electricity and oversized VFDs.
In this guide, we will walk through the engineering math required to size a conveyor motor and gearbox correctly, specifically focusing on the critical "Dynamic Tension" resulting from inertia.
Table of Contents
1. The Physics: Effective Pull (Te)
The first step in any sizing calculation is determining the Effective Pull (Te). This is the sum of all forces resisting the motion of the belt.
Te = Ffriction + Fgravity + Fmaterial
Where:
- Friction: Resistance from rollers, slider beds, and skirt seals.
- Gravity: The force required to lift the load (for inclined conveyors).
- Material: The force required to accelerate the material from zero to belt speed.
Note: In practice, friction and material acceleration usually dominate horizontal conveyor sizing, while gravity dominates inclined applications.
2. Calculating Motor Power
Once you have the Effective Pull (Te) in Newtons (or lbs) and the Belt Speed (v) in m/s (or fpm), calculating the required running power is straightforward.
Metric Units (kW)
P (kW) = (Te (N) × v (m/s)) / 1000
Imperial Units (HP)
P (HP) = (Te (lbs) × v (fpm)) / 33,000
📝 Worked Example: Sizing a Bulk Conveyor
Let's consider a horizontal belt conveyor transporting bulk material with the following parameters:
- Belt Speed (v): 1.5 m/s
- Total Effective Pull (Te): 3,200 N
- Startup Requirement: Full load start (High Inertia)
Step 1: Calculate Running Power
P = (3200 × 1.5) / 1000 = 4.8 kW
Step 2: Apply Service Factor
For a loaded start, we apply a service factor of 1.6 (Safety Margin).
Pmotor = 4.8 kW × 1.6 = 7.68 kW
Final Selection:
You generally have two options based on your control strategy:
1. 7.5 kW (10 HP) if using a VFD (controlled ramp).
2. 11 kW (15 HP) if using Direct-On-Line (DOL) starting to handle the immediate inrush current.
3. The Inertia Problem & VFDs
Your search data highlights a common struggle: "dynamic tension resulting from inertia." This tension spike occurs during the first few seconds of operation.
To accelerate a heavy load, the motor must overcome the Moment of Inertia (J) of the entire system. If you start a loaded conveyor "Across the Line" (Direct-On-Line), the sudden torque spike can snap belts or shear gearbox keys.
Comparison: Starting Methods
| Option | CapEx Cost | Mechanical Stress | Recommended? |
|---|---|---|---|
| DOL Starter | Low | Very High (Shock) | ❌ No (Unless Small) |
| Soft Starter | Medium | Medium | ⚠️ Acceptable |
| VFD (Inverter) | Higher | Low (Smooth Ramp) | ✅ Best Practice |
Recommended VFDs for Conveyor Motors
For high-inertia conveyors, a Variable Frequency Drive (VFD) is strongly recommended. By programming a 3-5 second acceleration ramp, you limit dynamic belt tension and protect the gearbox from shock loads.
Bonus: VFDs also reduce peak inrush current, lowering electrical infrastructure and breaker sizing requirements.
4. Gearbox Ratio Selection
Electric motors typically run at high speeds (e.g., 1750 RPM @ 60Hz). Conveyor head pulleys run much slower (e.g., 60 RPM). You need a gear reducer to match the speed and multiply the torque.
The Ratio Formula:
Ratio (i) = Motor RPM / Required Pulley RPM
Example: If you need 60 RPM at the pulley and have a 1750 RPM motor:
i = 1750 / 60 ≈ 29.1
You would select a standard 30:1 Gearbox.
Caution: Always verify the gearbox thermal rating and service factor (Class I, II, or III) specifically for conveyor duty cycles.
Recommended Tools for Maintenance
If you are troubleshooting existing conveyors, these tools are essential for diagnosing motor health.
Frequently Asked Questions
Why does conveyor motor torque spike at startup?
Torque spikes because the motor must overcome static friction (which is higher than rolling friction) and accelerate the system's total inertia from a standstill. This requires 150% to 200% of the rated running torque.
Is a VFD required for conveyor applications?
Not always, but VFDs are strongly recommended for high-inertia or loaded-start conveyors. They allow for a controlled acceleration ramp, which prevents belt snapping and protects the gearbox gears from shock loads.
How do I size a VFD for a conveyor motor?
VFDs are sized based on the motor’s rated current and voltage. Choose a VFD with at least 10–20% higher current rating than the motor to handle dynamic startup loads. This prevents overheating or tripping during acceleration.
This article is written by a mechanical design engineer with hands-on experience in industrial automation, conveyor system design, and motor sizing applications.
As an Amazon Associate, I earn from qualifying purchases.


Comments