The Cause: You solved the mechanical shock and the inrush current, but you drastically over-specified the solution. You paid for continuous frequency control when all you needed was a controlled ramp-up.
Mechanically, an AC induction motor is a brute-force device. Managing how it accelerates a heavy inertial mass requires understanding the electrical differences between voltage control and frequency control. This guide explains the physics of Soft Starters versus VFDs.
Table of Contents
1. The Physics of Starting: LRA vs FLA
When an AC induction motor is stationary, its internal resistance is extremely low. If you connect it directly to line power (Direct-On-Line / DOL), it draws Locked Rotor Amps (LRA). This is typically 600% to 800% of the motor's Full Load Amps (FLA).
Simultaneously, the motor outputs roughly 150% to 250% of its rated torque in a fraction of a second (depending on the NEMA design class). This violent acceleration destroys gearboxes, stretches roller chains, and causes severe mechanical fatigue on motor shafts.
2. Soft Starters: SCRs and the Torque Penalty
A Soft Starter controls inrush current by manipulating Voltage. It uses solid-state devices called Silicon Controlled Rectifiers (SCRs) to "chop" the AC sine wave, only letting a portion of the voltage through to the motor. As the motor accelerates, the SCRs open wider until the motor receives full line voltage.
Once at full speed, an internal bypass contactor closes, taking the SCRs out of the circuit. This means a soft starter generates very little heat during normal operation.
In an induction motor, starting torque is proportional to the square of the applied voltage. If a soft starter drops the starting voltage to 50% to limit inrush current, the starting torque drops to 25% of its normal capacity.
Because of this massive torque penalty, Soft Starters are excellent for high-inertia but low-friction loads (like centrifugal fans and water pumps). However, if you apply a soft starter to a heavily loaded inclined conveyor, the motor may simply stall, humming until the thermal overload trips.
3. VFDs: PWM, V/Hz Ratio, and Full Torque
A Variable Frequency Drive (VFD) takes a completely different approach. It alters both Voltage and Frequency simultaneously.
The VFD rectifies incoming AC power into a DC bus, then uses Insulated-Gate Bipolar Transistors (IGBTs) to fire rapid pulses of DC power—a process called Pulse Width Modulation (PWM)—to simulate a new AC sine wave at any frequency you desire.
The V/Hz Advantage
By keeping the Volts-per-Hertz ratio constant (e.g., 460V / 60Hz = 7.6 V/Hz), the magnetic flux inside the motor remains saturated. This allows a properly tuned VFD to deliver rated torque from zero speed without drawing excessive inrush current. The motor can slowly and smoothly tear a fully loaded conveyor belt from a dead stop.
However, VFDs come with significant engineering drawbacks:
- Continuous Heat: The IGBTs are always switching, generating continuous thermal losses that require active cooling.
- Harmonics & dv/dt: High-speed PWM switching creates severe voltage spikes (high dv/dt) and common-mode noise. This often requires expensive line reactors or shielded VFD cables to prevent interference with nearby PLCs.
- Bearing Fluting: Common-mode voltages can induce capacitive discharge through the motor bearings. This electrical arcing physically pits the steel bearing races (EDM pitting), destroying them prematurely.
4. Engineering Selection Matrix
| Parameter | Soft Starter | VFD (Variable Frequency Drive) |
|---|---|---|
| Starting Torque | Low (Drops via Voltage Squared) | High (Up to 150% at 0 RPM) |
| Speed Control | None (Starts and stops only) | Full continuous control (0 to 100+ Hz) |
| Heat Generation | Low (Only during ramp; bypassed at speed) | High (Continuous switching losses) |
| Harmonic Noise | Minimal (Only distorts during ramp) | High (Requires shielding or filters) |
| Best Application | Fans, Centrifugal Pumps, Compressors | Loaded Conveyors, Hoists, Mixers, CNC Spindles |
⚙️ Master Heavy Power Transmission
Designing industrial drive systems requires strict management of torque, inertia, and electrical limits. Explore our full engineering series:
- Shaft Loading: Overhung Load (OHL) Motor Shaft Calculations
- Gearbox Selection: Worm Gear vs Planetary Gearbox Efficiency
- Torque Limits: Ball Detent Torque Limiters & Overload Clutches
- Tension Dynamics: Conveyor Belt Tension Calculation (T1/T2)
You optimized the inrush current. Can you optimize the procurement cycle?
The Sheet Mechanic is the field manual for the chaotic space between the CAD model and the factory floor. Learn how to manage vendors, defend your designs, and prevent downstream project failures.
This article is written by a mechanical design engineer with over 25 years of experience in industrial automation, material handling, and power transmission specification.